BG™ Solutions FAQ
| How does Roxtec products compare with protection levels for Lightning Protection | The standard IEC-62305 Lightning Protections define protection levels and classes. |
| What frames can be used with BG™? | Currently S, SF, G, GHM, GO, CF8, CF32 and CF16 are certified for bonding and grounding applications. |
| How long does it take to install? | A reasonable time estimate for installation is 5-10 minutes per cable. |
| What cable preparation is required? | The same as for glands or any other EMC installation. |
| Technical data | |||||||||
| Module | Cable range (OJ & OA) |
|
Total Ampacity |
Approx. Eqv. AWG | |||||
| RM/CM 20w40 | 3,5-16,5 | 4 | 6200 | 64 | 11 | ||||
| RM/CM 20 | 4-14,5 | 8 | 12400 | 128 | 8 | ||||
| RM 30/CM 30w40 | 10-25 | 13.24 | 20522 | 184 | 6 | ||||
| RM/CM 40(10-32) | 9,5-32,5 | 21.04 | 32612 | 212 | 4 | ||||
| RM 60(24-54) | 24-54 | 42.2 | 65410 | 352 | 1 | ||||
| RM 90 | 48-71 | 42.2 | 65410 | 352 | 1 | ||||
| RM 120 | 67,5-99 | 42.2 | 65410 | 352 | 1 | ||||
| AC short circuit test | ||||||||||||||
| Module |
|
|
EN 50262,/A1,/A2 Armored cables Category B current req, 1sec | Tested to, A | ||||||||||
| RM/CM 20w40 | 1180 | 4 | 1530 | 6 | CatA,500 | 500 | ||||||||
| RM/CM 20 | 1180 | 3060 | 3480 | |||||||||||
| RM 30/CM 30w40 | 1530 | 6 | 1530 | 6 | 4000 | 4101 | ||||||||
| RM/CM 40(10-32) | 2450 | 6 | 2450 | 6 | 5400 | 5409 | ||||||||
| RM 60(24-54) | 4900 | 6 | 5050 | 9 | 7200 | 7495 | ||||||||
| RM 90 | 5050 | 9 | 5050 | 9 | 10400 | 15274 | ||||||||
| RM 120 | 5050 | 9 | 8030 | 9 | 10400 | 15274 | ||||||||
| Current Surge test | Retention | ||||||
| Module | IEC 62305 puls shape 10/350. Tested in rectangular RM frames to, kA |
|
|||||
| RM/CM 20w40 | 50 | 140 | >600 (12mm) | ||||
| RM/CM 20 | 100 | 130 | |||||
| RM 30/CM 30w40 | 100 | 250 | |||||
| RM/CM 40(10-32) | 100 | 350 | >800 (14,5mm) | ||||
| RM 60(24-54) | 200 (Life cycle test) | 400 | >1500 | ||||
| RM 90 | 200 | 450 | >2000 | ||||
| RM 120 | 200 | 450 | |||||